Residential Electrical
General Inspections for All Areas
- Check wiring methods (usually cable assemblies) for support and suitability for the conditions.
- Check cable installation through or parallel to framing members for ¼-inch (31.8mm) clearance or protective steel plates.
- Check boxes for suitability of use.
- Verify that boxes are installed in accessible locations for all junctions and outlets and pull points.
- Check that cables are secured to boxes.
- Check boxes for conductor fill.
- Check positioning of boxes intended to be flush with combustible and noncombustible finished surfaces.
- Check for splicing devices on all equipment grounding conductors within boxes and bonding connections to metal boxes.
- Check equipment grounding conductors for suitability and size.
- Check boxes used in floors, or for support of ceiling fans, for listing.
- Check recessed fixtures for clearances from combustibles and insulation.
Kitchen Area Inspections
- Check spacing of receptacles for walls and countertops including islands and peninsulas.
- Verify that a minimum of two 20-Amp small appliance branch circuits are used for kitchen receptacles.
- Verify that a wall switched lighting outlet is provided and wired on a general lighting circuit.
- Verify that properly sized circuits have been provided for specific kitchen appliances, such as dishwashers, disposers, ranges, cooktops, trash compactors, and the like.
- Check for additional small appliance branch circuits where there is more than one kitchen.
- Check for other outlets or appliances on small appliance branch circuits.
Dining Room Area Inspections
- Check receptacle outlets for proper spacing.
- Verify that all required receptacle outlets are supplied by small appliance branch circuits.
- Check for wall switch controlled lighting outlet on a general lighting circuit.
Bathroom Area Inspections
- Verify that receptacle outlets are installed adjacent to and within 36 inches (91.5 mm) of each basin.
- Verify that receptacles are supplied by dedicated 20 amp branch circuits.
- Check for a wall switch controlled lighting outlet on a general lighting circuit.
Other Habitable Area Inspections (Bedrooms, Family Rooms, Dens, etc.)
- Check receptacle outlets for proper spacing.
- Check for wall switch controlled lighting outlets (including switched receptacles).
Hallway Area Inspections
- Check for at least one wall switch controlled (or automatic, remote, or centrally controlled) lighting outlet.
- Verify that hallways 10 ft. (3.05 m) or more have at least one receptacle outlet.
Stairway Area Inspections
- Check for at least one wall switch controlled (or automatic, remote, or centrally controlled) lighting outlet.
- Verify that wall switches are provided at each floor level where there are six or more steps between levels.
Closet Area Inspections
- Check clearances between lighting fixtures and storage spaces if fixtures are installed.
Laundry Area Inspections
- Verify that at least one receptacle outlet is installed for the laundry.
- Verify that a dedicated 20 ampere circuit supplies the laundry outlet(s) and no other outlets.
- Check for a laundry receptacle outlet within 6 ft. (1.83m) of the intended appliance location.
- Check for proper branch circuit conductors, including equipment grounding conductors, for 240 volt dryers (if used).
- Verify that lighting outlets for the area are supplied from general lighting circuits.
Basement and Attic Area Inspections
- Verify that at least one receptacle outlet is provided in unfinished basement areas in addition to any receptacles installed for laundry equipment.
- Verify that a receptacle outlet is provided for servicing mechanical equipment, if any.
- Verify that individual branch circuits are supplied for central heating equipment, if any.
- Verify that a wall switch controlled lighting outlet or a lighting outlet containing a switch is provided at the entrance to equipment requiring servicing.
- Check accessible attics, attic entrances and scuttle holes for clearances from or protection of cable assemblies.
Garage Area Inspections (Attached or with Electric Power)
- Verify that at least one receptacle outlet is provided.
- Verify that a wall switch controlled lighting outlet is provided.
Outdoor Area Inspections
- Check for at least two receptacle outlets, one each at the front and back of a dwelling.
- Check for wall switch controlled (or remote, central, or automatic controlled) exterior lighting outlets at outdoor entrances or exits with grade-level access.
RESIDENTIAL SERVICES, FEEDERS AND SYSTEM GROUNDING
Services, Feeders and System Grounding Inspections
- Review calculation of service load and determine minimum size of service conductors.
- Verify that service disconnects and over current devices are located outside or inside nearest the point of entrance of the service conductors.
- Verify that service disconnects are grouped together, with no more than six in any one location.
- Check for proper accessibility, working clearances, and dedicated spaces around service equipment.
- Check service-entrance wiring methods for suitability, support, and protection from damage.
- Check for a proper drip loop and weatherhead on overhead services.
- Verify that the point of attachment is adequate and will provide required support and clearances above roofs and grade.
- Check service masts for adequate strength and support.
- Check for proper clearances of service conductors from building openings.
- Check underground service conductors for proper depth, fill, protection, marking, and allowances for ground movement.
- Determine which grounding electrodes are available, and verify that they are bonded together to form a rounding electrode system.
- Check any made electrodes for proper size, type, and installation.
- Verify that grounding electrode conductors are unspliced and protected and that any metal enclosures are bonded and electrically continuous.
- Check grounding electrode conductor(s) for proper sizing.
- Check grounding electrode connections for proper type for protection, and for accessibility.
- Verify that the main bonding jumper is installed and of the proper size and type.
- Verify that interior metal piping systems are bonded, that bonding jumpers are properly sized, and that continuity around removable devices is assured.
- Verify that service raceways and enclosures are properly bonded.
RESIDENTIAL ELECTRICAL FINAL
General Inspections for All Areas
- Check for correction of any deficiencies noted on previous inspections.
- Check positioning of boxes intended to be flush with combustible and noncombustible finished surfaces.
- Check for proper positioning of receptacles and faceplates on walls.
- Check for gaps around outlet boxes in walls.
- Verify that conductor terminations and splicing methods are compatible with conductor materials.
- Verify that receptacles are bonded to metal boxes and that receptacles, switches, and metal face plates are grounded.
- Check polarity of devices and fixtures.
- Check for splicing devices on all equipment grounding conductors within boxes and for bonding connections to metal boxes.
- Verify that device ratings are compatible with circuit and equipment ratings.
- Check for proper use of connecters and fittings and for protection of cables.
- Check for bushings for equivalent protection for cables entering boxes and other enclosures.
- Verify that unused openings in boxes and other enclosures are closed.
- Verify that appliances, motors, and other equipment are grounded.
- Check buried raceways and cables for proper burial depth.
- Check installation of listed equipment for compliance with manufacturer’s instructions.
- Verify that fire rating of assemblies has been restored at electrical penetrations.
- Check for disconnecting means on both permanently connected and cord and plug connected appliances.
Kitchen Area Inspections
- Check spacing of receptacles for walls and countertops, including islands and peninsulas.
- Verify that a minimum of two 20 amp small appliance branch circuits are used for kitchen receptacles.
- Verify that small appliance branch circuits are used only for receptacles in kitchen, dining room, pantry, and so forth.
- Verify that counter top receptacles are provided with GFCI protection.
- Verify that refrigeration equipment is supplied by a small appliance branch circuit or an individual branch circuit.
- Verify that a wall switched lighting outlet is provided and wired on a general lighting circuit.
- Verify that properly sized circuits are provided for specific kitchen appliances, such as dishwashers, disposers, rangers, cooktops, trash compactors, and the like.
- Check for proper type, length, and use of flexible cords for appliance connections.
Dining Room Area Inspections
- Check receptacle outlets for proper spacing.
- Verify that all required receptacle outlets are supplied by small appliance branch circuits.
- Check for wall switch controlled lighting outlet on a general lighting circuit.
Bathroom Area Inspections
- Verify that receptacle outlets are installed adjacent to and within 36 inches (91.4 mm) of each basin.
- Verify that receptacles are supplied by dedicated 20 amp branch circuits.
- Verify that bathroom receptacles are GFCI protected.
- Check for a wall switch controlled lighting outlet on a general lighting circuit.
Other Habitable Area Inspections (Bedrooms, Family Rooms, Dens, etc.)
- Check receptacle outlets for proper spacing.
- Check for wall switch controlled lighting outlets (including switched receptacles).
- Check for Arc-fault Circuit interrupter protection on bedroom circuits (Effective January 1, 2002).
Hallway Area Inspections
- Check for at least one wall switch controlled (or automatic, remote, or centrally controlled) lighting outlet.
- Verify that hallways continuous for 10 ft. (3.05 m) or more have at least one receptacle outlet.
Stairway Inspections
- Check for at least one wall switch controlled (or automatic, remote, or centrally controlled) lighting outlet.
- Verify that wall switches are provided at each floor level where there are six or more steps.
Closet Inspections
- Check clearances between lighting fixtures and storage spaces if fixtures are installed.
Laundry Area Inspections
- Verify that at least one receptacle outlet is installed for the laundry.
- Verify that a dedicated 20-A circuit supplies the laundry outlet(s) and no other outlets.
- Check for a laundry receptacle outlet within 6 ft. (1.83 m) of the intended appliance location.
- Check for proper receptacle ratings based on branch-circuit ratings, including receptacles for electric dryers (if used).
- Verify that lighting outlets for the area are supplied from general lighting circuits.
Basement and Attic Inspections
- Verify that at least one receptacle outlet is provided in unfinished basement areas in addition to any receptacles installed for laundry equipment.
- Verify that a receptacle outlet is provided for servicing mechanical equipment, if any.
- Verify that GFCI protection is provided for receptacles in unfinished portions of basements (other than receptacles for laundry, pumps, or specific appliances).
- Verify that individual branch circuits are supplied for central heating equipment, if any.
- Verify that a wall switch controlled lighting outlet or a lighting outlet containing a switch is provided at the entrance to equipment requiring servicing.
- Check accessible attics, attic entrances, and scuttle holes for clearances from or protection of cable assemblies.
Garage Inspections (Attached or with Electric Power)
- Verify that at least one receptacle outlet is provided.
- Verify that GFCI protection is provided for readily accessible receptacles, other than those for appliances in dedicated spaces.
- Verify that a wall switch controlled lighting outlet is provided.
Outdoor Inspections
- Check for at least two receptacle outlets, one each at front and back of dwelling.
- Verify that outdoor receptacles are GFCI protected unless they are not readily accessible and are supplied by circuits for deicing or snow-melting equipment.
- Check for wall switch controlled (or remote, central, or automatic controlled) exterior lighting outlets at outdoor entrances or exits with grade level access.
- Check for boxes at exterior fixture locations.
Service Equipment Inspections
- Review bonding and grounding if not completed during previous inspections.
- Check over current devices for compatibility with conductors (terminals, ratings, and ampacities).
- Check for proper identification of all over current devices and disconnects.
- Check for open spaces in panelboard fronts.
- Verify that doorbell and other Class 2 wiring and transformers are located in appropriate places (not in service equipment or panelboards).
- Verify that any back-fed over current devices are secured in place.